Installation Information
Water Piping Connections
Hot Water Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
COMPACT
Water Source/Geothermal Heat Pump
R-410A Refrigerant
Commercial 0.75-6 Ton
Envision
2
Compact Installation Manual
s
Page view 0
1 2 3 4 5 6 ... 59 60

Summary of Contents

Page 1 - Compact Installation Manual

IM1022ANA 05/14Installation InformationWater Piping ConnectionsHot Water ConnectionsElectricalStartup ProceduresTroubleshootingPreventive Maintenanc

Page 2

10ENVISION2 COMPACT INSTALLATION MANUALInstalling Horizontal UnitsRemove and discard the compressor hold down shipping bolt located at the front of th

Page 3 - Table of Contents

11ENVISION2 COMPACT INSTALLATION MANUALHanger Bracket LocationsBCAHEDGFLeftDEFGRightVibration IsolatorWasherHex Nuts(not supplied)Bolt andLockwasher3/

Page 4 - Model Nomenclature

12ENVISION2 COMPACT INSTALLATION MANUALAn air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct conne

Page 5 - Installing Vertical Units

13ENVISION2 COMPACT INSTALLATION MANUALIn ground water situations where scaling could be heavy or where biological growth such as iron bacteria will b

Page 6 - Vertical Dimensional Data

14ENVISION2 COMPACT INSTALLATION MANUALTypical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water

Page 7 - Vertical Disconnect

15ENVISION2 COMPACT INSTALLATION MANUALThe heat reclaiming hot water generator coil is of vented double-wall copper construction and is suitable for p

Page 8 - Horizontal Dimensional Data

16ENVISION2 COMPACT INSTALLATION MANUALCAUTION: Never operate the HWG circulating pump while dry. If the unit is placed in operation before the hot wa

Page 9 - Horizontal Disconnect

17ENVISION2 COMPACT INSTALLATION MANUAL208 Volt OperationAll 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red a

Page 10 - Installing Horizontal Units

18ENVISION2 COMPACT INSTALLATION MANUALElectrical DataPSC MotorModelRatedVoltageVoltageMin/MaxCompressorBlowerMotorFLATotalUnitFLAMinCircAmpMax Fuse/H

Page 11 - Hanger Bracket Locations

19ENVISION2 COMPACT INSTALLATION MANUALElectrical Data cont.5-Speed ECM MotorModelRatedVoltageVoltageMin/MaxCompressorBlowerMotorFLATotalUnitFLAMinCir

Page 13 - System Cleaning and Flushing

20ENVISION2 COMPACT INSTALLATION MANUALElectrical Data cont.CAUTION: When installing a unit with a variable speed ECM blower motor in 460/60/3 voltage

Page 14 - COMPACT INSTALLATION MANUAL

21ENVISION2 COMPACT INSTALLATION MANUALBlower Performance DataPSC BLOWER MOTOR BODYHIGHLOWMEDIUMBLOWER SPEED WIREStandard PSC MotorModelBlowerSpdBlowe

Page 15 - Plumbing Installation

22ENVISION2 COMPACT INSTALLATION MANUALBlower Performance Data cont.About 5-Speed ECM ConstantTorque MotorsThe 5-speed ECM is a ‘Constant Torque’ ECM

Page 16 - Hot Water Generator Startup

23ENVISION2 COMPACT INSTALLATION MANUALBlower Performance Data cont.LGNCHigh VoltageConnections3/16 in. 12345G - BlueY1 - RedAUX - GrayC - BlackL - Or

Page 17 - Freeze Detection

24ENVISION2 COMPACT INSTALLATION MANUALBlower Performance Data cont.Variable Speed ECM MotorSingle SpeedModelMaxESPBlower SizeMotor hpAirfl ow DIP S

Page 18 - Electrical Data

25ENVISION2 COMPACT INSTALLATION MANUALBlower Performance Data cont.The ABC board’s Yellow Confi g LED will fl ash the current variable speed ECM blower

Page 19 - Electrical Data cont

26ENVISION2 COMPACT INSTALLATION MANUALWiring SchematicsAurora Control 460/60/3 Variable Speed ECM97P818-08 3/19/12ThermistorRelay CoilSwitch - C

Page 20

27ENVISION2 COMPACT INSTALLATION MANUALWiring Schematics cont.Aurora Base Control 460/60/3 5-Speed ECM with ReheatSlow FlashFast FlashFlash CodeStatus

Page 21 - Blower Performance Data

28ENVISION2 COMPACT INSTALLATION MANUALWiring Schematics cont.To ABC - P8YellowBrownGreenBlueWhiteBlackOrangeRedDevices Must Be Wired inDaisy Chain Co

Page 22 - Blower Performance Data cont

29ENVISION2 COMPACT INSTALLATION MANUALControls - Aurora Base ControlAurora ‘Base’ ControlNOTE: Refer to the Aurora Base Control Application and Troub

Page 23

ENVISION2 COMPACT INSTALLATION MANUALTable of ContentsModel Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 24

30ENVISION2 COMPACT INSTALLATION MANUALCycle with Blower - The accessory relay will cycle with the blower output.Cycle with Compressor - The accessory

Page 25

31ENVISION2 COMPACT INSTALLATION MANUALOver/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the ra

Page 26 - Wiring Schematics

32ENVISION2 COMPACT INSTALLATION MANUALCC2FactoryFaultALGALMLSESACC cStatusAuroraTM BaseControlRV – K1CC2CC – K2CC Hi – K3Fan – K4Alarm – K5Acc – K6AC

Page 27 - Wiring Schematics cont

33ENVISION2 COMPACT INSTALLATION MANUALThe Aurora Unitary Protocol Converter (UPC) is designed to add-on to any Aurora based heat pump control. The Au

Page 28 - ZS Sensor Information

34ENVISION2 COMPACT INSTALLATION MANUALAurora UPC Features• Rugged enclosure made of GE C2950 Cycoloy plastic• Built-in surge transient protection c

Page 29 - Other Control Features

35ENVISION2 COMPACT INSTALLATION MANUALPort 1a is used to communicate to the Building Automation System (BAS). This port’s settings are configured thr

Page 30 - Safety Features

36ENVISION2 COMPACT INSTALLATION MANUAL1. Leaving Air Temperature (LAT) Sensor – This 10 kOhm NTC sensor is factory installed on all UPC equipped hea

Page 31 - Operation Description

37ENVISION2 COMPACT INSTALLATION MANUALStatus LED (LED3, Green)Description of Operation Fault LED, GreenNormal Mode ONControl is Non-functional OFFTes

Page 32 - ABC Control Board Layout

38ENVISION2 COMPACT INSTALLATION MANUAL1. Accessory Relay2 – A second, configurable, accessory relay on the AXB is provided that can be cycled with t

Page 33

39ENVISION2 COMPACT INSTALLATION MANUAL1. Energy Monitoring (Standard Sensor Kit on ‘Advanced’ models) - The Energy Monitoring Kit includes two curre

Page 34 - Aurora UPC Optional Features

4ENVISION2 COMPACT INSTALLATION MANUALModel Nomenclature1-2 3 4-6 7 8 9Model Type NB – Envision2 CompactCabinet Configuration V – Vertical H - H

Page 35

40ENVISION2 COMPACT INSTALLATION MANUALZS Series RNet Sensor OverviewThe ZS Series line of intelligent zone sensors provides the function and flexibil

Page 36 - Fault LED (LED1, Red)

41ENVISION2 COMPACT INSTALLATION MANUALRNet Sensor Physical and Electrical DataSensing Element Range AccuracyTemperature (on non-Humidity models) -

Page 37 - Status LED (LED3, Green)

42ENVISION2 COMPACT INSTALLATION MANUAL• High voltage is correct and matches nameplate.• Fuses, breakers and wire size correct.• Low voltage wiring

Page 38

43ENVISION2 COMPACT INSTALLATION MANUALOperating LimitsOperating LimitsCooling Heating(°F) (°C) (°F) (°C)Air Limits Min. Ambient Air 45 7.2 45 7.2 R

Page 39

44ENVISION2 COMPACT INSTALLATION MANUALOperating Parameters cont.Dual Capacity ModelsFirst Stage OperationEntering Water Temp °FWater Flowgpm/tonCool

Page 40

45ENVISION2 COMPACT INSTALLATION MANUALPressure DropSingle SpeedModel gpmPressure Drop (psi)Valve gpm CvPressure Drop (psi)30°F 50°F 70°F 90°F 110°F00

Page 41

46ENVISION2 COMPACT INSTALLATION MANUALSymptomHead PressureSuction PressureCompressorAmp DrawSuperheat SubcoolingAir Temp. DifferentialWater Temp. Dif

Page 42 - Unit Startup

47ENVISION2 COMPACT INSTALLATION MANUALCompressor ResistanceModel208-230/60/1 265/60/1208-230/60/3 460/60/3 575/60/3Run Start Run StartSingle Speed009

Page 43 - Operating Parameters

48ENVISION2 COMPACT INSTALLATION MANUALHeat of Extraction/Rejection DataSingle SpeedModel gpmHeat of Extraction (HE) - MBtu/h Heat of Rejection (HR) -

Page 44 - Operating Parameters cont

49ENVISION2 COMPACT INSTALLATION MANUALShould a major problem develop, refer to the following information for possible causes and corrective steps.If

Page 45 - Pressure Drop

5ENVISION2 COMPACT INSTALLATION MANUALWARNING: Before performing service or maintenance operations on a system, turn off main power switches to the in

Page 46 - Reference Calculations

50ENVISION2 COMPACT INSTALLATION MANUALCheck One Start up/Check-out for new installation ❑ Troubleshooting Problem:_____________________

Page 47 - Thermistor Resistance

51ENVISION2 COMPACT INSTALLATION MANUALCOOLING CYCLE ANALYSISHot WaterGenerator-EXPANSIONVALVEAIRCOIL°FPSI°FPSIBRINE INBRINE OUTBRINE INBRINE OUTCOMPR

Page 48 - Dual Capacity

52ENVISION2 COMPACT INSTALLATION MANUALWater Coil Maintenance1. Keep all air out of the water. An open loop system should be checked to ensure that t

Page 49 - Troubleshooting

53ENVISION2 COMPACT INSTALLATION MANUALService PartsPart DescriptionSingle Speed Vertical Units009 012 015 018 024 030 036 042 048 060 070CompressorCo

Page 50

54ENVISION2 COMPACT INSTALLATION MANUALService Parts cont.Part DescriptionSingle Speed Horizontal Units009 012 015 018 024 030 036 042 048 060 070Comp

Page 51 - Startup/7roubleshooting Form

55ENVISION2 COMPACT INSTALLATION MANUALService Parts cont.Part DescriptionDual Capacity Vertical Units Dual Capacity Horizontal Units026 038 049 064 0

Page 52 - Replacement Parts

56ENVISION2 COMPACT INSTALLATION MANUALNotes

Page 53 - Service Parts

57ENVISION2 COMPACT INSTALLATION MANUALRevision GuidePages: Description: Date: By:All Updated with All-Aluminum Air Coils 19 May 2014 DS33-41 Added Au

Page 56

6ENVISION2 COMPACT INSTALLATION MANUALVertical Dimensional Data12834ACCESSPANELAir coilAIR COIL SIDEAIR COIL SIDEAir coil5Power supply1 in (25.4 mm)kn

Page 57 - Revision Guide

Manufactured byWaterFurnace International, Inc.9000 Conservation WayFort Wayne, IN 46809www.waterfurnace.com©2014 WaterFurnace International, Inc., 90

Page 58

7ENVISION2 COMPACT INSTALLATION MANUALVertical Dimensional Data cont.LL1.8 in.[4.6 cm]AlternativePowerLocation Disconnect Located on thisSide for a Ri

Page 59

8ENVISION2 COMPACT INSTALLATION MANUALHorizontal Dimensional DataRight Return End DischargeLeft ReturnEnd Discharge End DischargeEnd DischargeSide Dis

Page 60 - IM1022ANA 05/14

9ENVISION2 COMPACT INSTALLATION MANUALHorizontal Dimensional Data cont.2.1 in.[5.3 cm]KKDisconnect Locatedon this Side for aLeft Return DisconnectLoca